dc.contributor.author |
Papathanassiou, SA |
en |
dc.contributor.author |
Papadopoulos, MP |
en |
dc.date.accessioned |
2014-03-01T01:24:29Z |
|
dc.date.available |
2014-03-01T01:24:29Z |
|
dc.date.issued |
2006 |
en |
dc.identifier.issn |
0885-8977 |
en |
dc.identifier.uri |
https://dspace.lib.ntua.gr/xmlui/handle/123456789/17282 |
|
dc.subject |
Harmonics modeling |
en |
dc.subject |
Power system harmonics |
en |
dc.subject |
Summation of harmonics |
en |
dc.subject |
Wind turbines |
en |
dc.subject.classification |
Engineering, Electrical & Electronic |
en |
dc.subject.other |
Electric currents |
en |
dc.subject.other |
Electric distortion |
en |
dc.subject.other |
Harmonic analysis |
en |
dc.subject.other |
Mathematical models |
en |
dc.subject.other |
Wind power |
en |
dc.subject.other |
Wind turbines |
en |
dc.subject.other |
Harmonic impedance |
en |
dc.subject.other |
Harmonic load flow |
en |
dc.subject.other |
Power system harmonics |
en |
dc.subject.other |
Voltage distortion |
en |
dc.subject.other |
Electric power systems |
en |
dc.title |
Harmonic analysis in a power system with wind generation |
en |
heal.type |
journalArticle |
en |
heal.identifier.primary |
10.1109/TPWRD.2005.864063 |
en |
heal.identifier.secondary |
http://dx.doi.org/10.1109/TPWRD.2005.864063 |
en |
heal.language |
English |
en |
heal.publicationDate |
2006 |
en |
heal.abstract |
Variable-speed wind turbines inject harmonic currents in the network, which may potentially create voltage distortion problems. In this paper, a case study is presented for a 10-MW wind farm, intended to be connected to a network with extended high-voltage submarine cable lines. First, the system modeling approach and the harmonic load-flow calculation is described. Then, the harmonic impedance of the system is calculated for a variety of configurations and operating conditions, and its main characteristics are discussed. Harmonic load-flow calculations are provided to indicate potential voltage distortion problems. A simplified methodology, suggested in relevant IEC publications, is applied to the system and its results are compared to those of the harmonic load flow. A discussion on the summation of harmonic currents within a wind farm is also included. © 2006 IEEE. |
en |
heal.publisher |
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC |
en |
heal.journalName |
IEEE Transactions on Power Delivery |
en |
dc.identifier.doi |
10.1109/TPWRD.2005.864063 |
en |
dc.identifier.isi |
ISI:000241049900033 |
en |
dc.identifier.volume |
21 |
en |
dc.identifier.issue |
4 |
en |
dc.identifier.spage |
2006 |
en |
dc.identifier.epage |
2016 |
en |