HEAL DSpace

Harmonic analysis in a power system with wind generation

Αποθετήριο DSpace/Manakin

Εμφάνιση απλής εγγραφής

dc.contributor.author Papathanassiou, SA en
dc.contributor.author Papadopoulos, MP en
dc.date.accessioned 2014-03-01T01:24:29Z
dc.date.available 2014-03-01T01:24:29Z
dc.date.issued 2006 en
dc.identifier.issn 0885-8977 en
dc.identifier.uri https://dspace.lib.ntua.gr/xmlui/handle/123456789/17282
dc.subject Harmonics modeling en
dc.subject Power system harmonics en
dc.subject Summation of harmonics en
dc.subject Wind turbines en
dc.subject.classification Engineering, Electrical & Electronic en
dc.subject.other Electric currents en
dc.subject.other Electric distortion en
dc.subject.other Harmonic analysis en
dc.subject.other Mathematical models en
dc.subject.other Wind power en
dc.subject.other Wind turbines en
dc.subject.other Harmonic impedance en
dc.subject.other Harmonic load flow en
dc.subject.other Power system harmonics en
dc.subject.other Voltage distortion en
dc.subject.other Electric power systems en
dc.title Harmonic analysis in a power system with wind generation en
heal.type journalArticle en
heal.identifier.primary 10.1109/TPWRD.2005.864063 en
heal.identifier.secondary http://dx.doi.org/10.1109/TPWRD.2005.864063 en
heal.language English en
heal.publicationDate 2006 en
heal.abstract Variable-speed wind turbines inject harmonic currents in the network, which may potentially create voltage distortion problems. In this paper, a case study is presented for a 10-MW wind farm, intended to be connected to a network with extended high-voltage submarine cable lines. First, the system modeling approach and the harmonic load-flow calculation is described. Then, the harmonic impedance of the system is calculated for a variety of configurations and operating conditions, and its main characteristics are discussed. Harmonic load-flow calculations are provided to indicate potential voltage distortion problems. A simplified methodology, suggested in relevant IEC publications, is applied to the system and its results are compared to those of the harmonic load flow. A discussion on the summation of harmonic currents within a wind farm is also included. © 2006 IEEE. en
heal.publisher IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC en
heal.journalName IEEE Transactions on Power Delivery en
dc.identifier.doi 10.1109/TPWRD.2005.864063 en
dc.identifier.isi ISI:000241049900033 en
dc.identifier.volume 21 en
dc.identifier.issue 4 en
dc.identifier.spage 2006 en
dc.identifier.epage 2016 en


Αρχεία σε αυτό το τεκμήριο

Αρχεία Μέγεθος Μορφότυπο Προβολή

Δεν υπάρχουν αρχεία που σχετίζονται με αυτό το τεκμήριο.

Αυτό το τεκμήριο εμφανίζεται στην ακόλουθη συλλογή(ές)

Εμφάνιση απλής εγγραφής