HEAL DSpace

Performance of a solar driven compound NH3/H2OH2O/LiBr absorption refrigeration system in athens

Αποθετήριο DSpace/Manakin

Εμφάνιση απλής εγγραφής

dc.contributor.author Kouremenos, DA en
dc.contributor.author Antonopoulos, KA en
dc.contributor.author Rogdakis, E en
dc.date.accessioned 2014-03-01T01:40:00Z
dc.date.available 2014-03-01T01:40:00Z
dc.date.issued 1990 en
dc.identifier.issn 0741983X en
dc.identifier.uri https://dspace.lib.ntua.gr/xmlui/handle/123456789/23051
dc.relation.uri http://www.scopus.com/inward/record.url?eid=2-s2.0-0025564562&partnerID=40&md5=9ad35c0151954e4cbaaa9bc6f06a447d en
dc.subject.other Data Processing--Natural Sciences Applications en
dc.subject.other Refrigerating Machinery--Absorption en
dc.subject.other Solar Radiation--Calculations en
dc.subject.other Coefficient of Performance en
dc.subject.other Compound System en
dc.subject.other Refrigeration en
dc.title Performance of a solar driven compound NH3/H2OH2O/LiBr absorption refrigeration system in athens en
heal.type journalArticle en
heal.publicationDate 1990 en
heal.abstract A solar driven, high efficiency, compound refrigeration system is considered, made up of two cooperating absorption parts, which use NH3/H2O and H2O/LiBr solutions, respectively. Solar heat is given to the vapour generator of the NH3/H2O unit, and the heat produced by the absorber and the condenser of this unit is supplied to the vapour generator of the H2O/LiBr unit. A method for simulating the operation of the compound system has been developed and applied for predicting the hour by hour performance of the system operating during the typical year in Athens, for which solar radiation and ambient temperature data are available. An optimization study for the compound and the individual cycles has also been made. Very high performance of the system has been predicted. For example, on 21 May, the calculated theoretical coefficient of performance is 219% while the corresponding theoretical values of single H2O/LiBr and NH3/H2O units are 93% and 65% respectively. The corresponding calculated cooling power produced by the system is 543 W/m2-collector. An annual analysis shows that the cooling produced by a NH3/H2O unit in Athens is 0.87 GJ/m2-year, while the present compound system gives an impressive increase to 3 GJ/m2-year. © 1990. en
heal.journalName Solar and Wind Technology en
dc.identifier.volume 7 en
dc.identifier.issue 6 en
dc.identifier.spage 685 en
dc.identifier.epage 697 en