HEAL DSpace

Techno-economic evaluation of reduction of low-voltage bushings diameter in single-phase distribution transformers

Αποθετήριο DSpace/Manakin

Εμφάνιση απλής εγγραφής

dc.contributor.author Olivares-Galvan, JC en
dc.contributor.author Magdaleno-Adame, S en
dc.contributor.author Campero-Littlewood, E en
dc.contributor.author Escarela-Perez, R en
dc.contributor.author Georgilakis, PS en
dc.date.accessioned 2014-03-01T02:04:11Z
dc.date.available 2014-03-01T02:04:11Z
dc.date.issued 2011 en
dc.identifier.issn 15325008 en
dc.identifier.uri https://dspace.lib.ntua.gr/xmlui/handle/123456789/29401
dc.subject bushings en
dc.subject efficiency en
dc.subject finite element method en
dc.subject load losses en
dc.subject low-voltage conductor en
dc.subject pole-mounted distribution transformer en
dc.subject tank wall en
dc.subject total owning cost en
dc.subject.other Distribution transformer en
dc.subject.other Finite Element en
dc.subject.other Low-voltage en
dc.subject.other Tank walls en
dc.subject.other total owning cost en
dc.subject.other Electric load loss en
dc.subject.other Electric transformers en
dc.subject.other Finite element method en
dc.subject.other Magnetic materials en
dc.subject.other Tanks (containers) en
dc.subject.other Bushings en
dc.title Techno-economic evaluation of reduction of low-voltage bushings diameter in single-phase distribution transformers en
heal.type journalArticle en
heal.identifier.primary 10.1080/15325008.2011.584109 en
heal.identifier.secondary http://dx.doi.org/10.1080/15325008.2011.584109 en
heal.publicationDate 2011 en
heal.abstract The contributions of this article are the analysis and economic evaluation of the impact on tank wall losses of a diameter reduction of low-voltage bushings of pole-mounted single-phase distribution transformers. Finite element simulations of 5- to 167-kVA transformers were performed. The study was motivated when bushing manufacturers reduced diameter from 4.6 to 3.6 cm. Results show that when the diameter of low-voltage bushings is reduced, (i) load losses increase and (ii) total owning cost decreases for transformers up to 15 kVA and increases for transformers of 25-167 kVA. The insertion of non-magnetic material between bushing holes is also evaluated. Copyright © Taylor & Francis Group, LLC. en
heal.journalName Electric Power Components and Systems en
dc.identifier.doi 10.1080/15325008.2011.584109 en
dc.identifier.volume 39 en
dc.identifier.issue 13 en
dc.identifier.spage 1388 en
dc.identifier.epage 1402 en


Αρχεία σε αυτό το τεκμήριο