HEAL DSpace

Thermal effect of the recloser operation cycle on bare overhead conductors

Αποθετήριο DSpace/Manakin

Εμφάνιση απλής εγγραφής

dc.contributor.author Halevidis, CD en
dc.contributor.author Karagiannopoulos, CG en
dc.contributor.author Bourkas, PD en
dc.date.accessioned 2014-03-01T02:14:50Z
dc.date.available 2014-03-01T02:14:50Z
dc.date.issued 2012 en
dc.identifier.issn 08858977 en
dc.identifier.uri https://dspace.lib.ntua.gr/xmlui/handle/123456789/30146
dc.subject Automatic circuit reclosers en
dc.subject medium-voltage distribution systems en
dc.subject multiple short circuits en
dc.subject overhead bare conductors en
dc.subject short-circuit current en
dc.subject thermal effect en
dc.subject.other Calculation methods en
dc.subject.other Distribution systems en
dc.subject.other Equivalent thermal en
dc.subject.other Heating process en
dc.subject.other Medium voltage en
dc.subject.other Numerical solution en
dc.subject.other Operation cycles en
dc.subject.other Overhead conductors en
dc.subject.other Reclosers en
dc.subject.other Reclosing en
dc.subject.other Temperature rise en
dc.subject.other Tripping operation en
dc.subject.other Electric power transmission en
dc.subject.other Thermal effects en
dc.subject.other Electrical engineering en
dc.title Thermal effect of the recloser operation cycle on bare overhead conductors en
heal.type journalArticle en
heal.identifier.primary 10.1109/TPWRD.2012.2183682 en
heal.identifier.secondary http://dx.doi.org/10.1109/TPWRD.2012.2183682 en
heal.identifier.secondary 6156493 en
heal.publicationDate 2012 en
heal.abstract A new calculation method of the temperature rise generated from multiple (consecutive) short circuits, to which bare overhead conductors are subjected, is proposed in this paper. Multiple short circuits are common in medium-voltage lines protected by reclosers due to their operation cycle. The proposed method treats each short circuit as a separate event. In additiony, the cooling between each short circuit is taken into account. The results of the proposed method are compared to the results given by the method of the IEC 60865-1 standard. The application of the proposed method results in greater temperature rises when the equivalent thermal current density is greater than a threshold. Furthermore, alterations to the recloser operation cycle are performed in order to investigate its effect on the generated temperature rise, namely, alterations to the reclosing interval between successive tripping operations and the ratio of fast to delayed trips. Finally, the proposed method was compared to an exact numerical solution of the heating process. © 2012 IEEE. en
heal.journalName IEEE Transactions on Power Delivery en
dc.identifier.doi 10.1109/TPWRD.2012.2183682 en
dc.identifier.volume 27 en
dc.identifier.issue 2 en
dc.identifier.spage 568 en
dc.identifier.epage 574 en