HEAL DSpace

Flux distribution analysis in three-phase Si-Fe wound transformer cores

Αποθετήριο DSpace/Manakin

Εμφάνιση απλής εγγραφής

dc.contributor.author Loizos, G en
dc.contributor.author Kefalas, TD en
dc.contributor.author Kladas, AG en
dc.contributor.author Souflaris, AT en
dc.date.accessioned 2014-03-01T02:46:47Z
dc.date.available 2014-03-01T02:46:47Z
dc.date.issued 2010 en
dc.identifier.issn 0018-9464 en
dc.identifier.uri https://dspace.lib.ntua.gr/xmlui/handle/123456789/32858
dc.subject Magnetic cores en
dc.subject Magnetic field measurement en
dc.subject Magnetic losses en
dc.subject Power transformers en
dc.subject.classification Engineering, Electrical & Electronic en
dc.subject.classification Physics, Applied en
dc.subject.other Core loss en
dc.subject.other FEM analysis en
dc.subject.other Flux densities en
dc.subject.other Flux distributions en
dc.subject.other Magnetic behavior en
dc.subject.other Magnetic flux densities en
dc.subject.other Magnetic loss en
dc.subject.other Magnetic losses en
dc.subject.other Nonuniform en
dc.subject.other Third harmonic components en
dc.subject.other Time variations en
dc.subject.other Transformer core en
dc.subject.other Electric field measurement en
dc.subject.other Magnetic circuits en
dc.subject.other Magnetic cores en
dc.subject.other Magnetic devices en
dc.subject.other Magnetic field measurement en
dc.subject.other Magnetic fields en
dc.subject.other Magnetic flux en
dc.subject.other Magnetostriction en
dc.subject.other Transformer substations en
dc.subject.other Power transformers en
dc.title Flux distribution analysis in three-phase Si-Fe wound transformer cores en
heal.type conferenceItem en
heal.identifier.primary 10.1109/TMAG.2009.2033022 en
heal.identifier.secondary 5393109 en
heal.identifier.secondary http://dx.doi.org/10.1109/TMAG.2009.2033022 en
heal.language English en
heal.publicationDate 2010 en
heal.abstract This paper shows experimental results of longitudinal flux density and its harmonics at the limb, the yoke and the corner of a three-phase, Si-Fe, five-legged wound transformer core. Results show that the flux density is nonuniform in the cores and there is high level of third harmonic component. Moreover, the lower flux values in the outer cores have been assessed and the simultaneous time variation of the flux in both outer cores has been demonstrated by measurements while the peak magnetic flux density values have been compared to FEM analysis. These findings enable a better understanding of the magnetic behavior of five-legged wound transformer cores and their consideration is expected to achieve respective improvement of the design with respect to core losses and magnetostriction noise. © 2010 IEEE. en
heal.publisher IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC en
heal.journalName IEEE Transactions on Magnetics en
dc.identifier.doi 10.1109/TMAG.2009.2033022 en
dc.identifier.isi ISI:000273765400109 en