dc.contributor.author |
Vournas, CD |
en |
dc.date.accessioned |
2014-03-01T02:47:38Z |
|
dc.date.available |
2014-03-01T02:47:38Z |
|
dc.date.issued |
1985 |
en |
dc.identifier.uri |
https://dspace.lib.ntua.gr/xmlui/handle/123456789/33301 |
|
dc.relation.uri |
http://www.scopus.com/inward/record.url?eid=2-s2.0-0022176387&partnerID=40&md5=e5c0fab64988a2358c2c3bb281f6ec9f |
en |
dc.subject.other |
ELECTRIC MACHINERY - Oscillations |
en |
dc.subject.other |
CONTROLLER GAINS |
en |
dc.subject.other |
CONTROLLER PARAMETERS |
en |
dc.subject.other |
ELECTROMECHANICAL OSCILLATIONS |
en |
dc.subject.other |
GENERATOR CONTROLLERS |
en |
dc.subject.other |
MULTIMACHINE POWER SYSTEMS |
en |
dc.subject.other |
ELECTRIC POWER SYSTEMS |
en |
dc.title |
OPTIMIZATION OF CONTROLLER PARAMETERS IN A MULTIMACHINE POWER SYSTEM. |
en |
heal.type |
conferenceItem |
en |
heal.publicationDate |
1985 |
en |
heal.abstract |
The problem of undamped electromechanical oscillations in a power system has been attacked in this paper with a new technique for the coordination of the generator controllers, before the installation of power system stabilizers. A parameter optimization algorithm has been derived in which a frequency domain quantity, the real part of the critical eigenvalue, is to be minimized. The algorithm consists of a steepest descent in conjunction with a variable step method specially designed for the class of problems encountered. The algorithm does not yield an oveall optimum; the values reached, however, are adequate for the stabilization of an initially unstable power system. |
en |
heal.publisher |
IEE, London, Engl |
en |
heal.journalName |
IEE Conference Publication |
en |
dc.identifier.issue |
252 |
en |
dc.identifier.spage |
72 |
en |
dc.identifier.epage |
77 |
en |