dc.contributor.author |
Olivares-Galvan, JC |
en |
dc.contributor.author |
Escarela-Perez, R |
en |
dc.contributor.author |
Georgilakis, PS |
en |
dc.contributor.author |
Campero-Littlewood, E |
en |
dc.date.accessioned |
2014-03-01T02:52:45Z |
|
dc.date.available |
2014-03-01T02:52:45Z |
|
dc.date.issued |
2010 |
en |
dc.identifier.uri |
https://dspace.lib.ntua.gr/xmlui/handle/123456789/36041 |
|
dc.subject |
Distribution transformers |
en |
dc.subject |
Eddy current losses |
en |
dc.subject |
Hysteresis losses |
en |
dc.subject |
Iron-core losses |
en |
dc.subject |
Loss separation |
en |
dc.subject |
No-load test |
en |
dc.subject |
Two frequency method |
en |
dc.subject |
Twotemperature method |
en |
dc.subject.other |
Distribution transformer |
en |
dc.subject.other |
Eddy current losses |
en |
dc.subject.other |
Hysteresis losses |
en |
dc.subject.other |
Iron-core losses |
en |
dc.subject.other |
Loss separation |
en |
dc.subject.other |
No-load test |
en |
dc.subject.other |
Two-frequency method |
en |
dc.subject.other |
Two-temperature |
en |
dc.subject.other |
Eddy currents |
en |
dc.subject.other |
Electric load loss |
en |
dc.subject.other |
Electric transformer testing |
en |
dc.subject.other |
Energy conversion |
en |
dc.subject.other |
Hysteresis |
en |
dc.subject.other |
Magnetic cores |
en |
dc.subject.other |
Asynchronous machinery |
en |
dc.title |
Separation of no-load losses for distribution transformers using experimental methods: Two frequencies and two temperatures |
en |
heal.type |
conferenceItem |
en |
heal.identifier.primary |
10.1049/cp.2010.0900 |
en |
heal.identifier.secondary |
http://dx.doi.org/10.1049/cp.2010.0900 |
en |
heal.publicationDate |
2010 |
en |
heal.abstract |
This paper presents an investigation on the separation of no-load losses into hysteresis and eddy current losses. The two-temperatures and the two-frequency methods are used to separate the losses in a transformer core. Two measurements are required for the calculation of the eddy and hysteresis losses. The methodologies are applied to a commercial 15 kVA shell-type, single-phase distribution transformer, with core lamination thickness of 0.23 mm. The main contribution of this paper is the presentation of a practical and validated example for the accurate computation of eddy current losses and hysteresis losses in distribution transformers. |
en |
heal.journalName |
IET Conference Publications |
en |
dc.identifier.doi |
10.1049/cp.2010.0900 |
en |
dc.identifier.volume |
2010 |
en |
dc.identifier.issue |
572 CP |
en |